Huguenot Labs can also complete an Inductively Coupled Plasma Mass Spectrometry (ICP-MS) on the material removed from the surface of the pipe. This ICP-MS test is a very powerful tool for trace Part’s Per Billion- Parts Per Million (ppb-ppm) and ultra-trace (ppm-ppb) elemental analysis. The Pipe analysis and ICP-MS test does not determine if the pipe was manufactured to ASTM requirements. It does however give you a detailed breakdown of the material being removed from the walls of the pipe due to corrosion and/or MIC. Included in this test is “Stereomicroscopic” photos giving a visual view of the deposit analysis.
Sample ICP-MS Analysis Report:
COMPANY ID: Sample ICP-MS Analysis Report
REQUESTED BY: Tim O’Leary
SAMPLE NO: 110205-2
DATE: 11-27-05
ANALYSIS REQUESTED: Analyze sample from sprinkler pipe.
PHYSICAL ANALYSIS:
APPEARANCE: Reddish brown powder-like particles. See photograph # 1.
MICROSCOPIC ANALYSIS: See attached Stereomicroscopic pictures # 2 thru 5.
ORGANIC ANALYSIS: No organic extraction was performed.
INORGANIC ANALYSIS:
PROCEDURE: The deposit was initially ashed at 550oC and then fused at 950°C. The fused
sample was solubilized and then analyzed by Inductively Coupled Plasma
(ICP) Spectroscopy. The ICP elemental results for a sample was converted to
their oxides and normalized to 100% for reporting.
| ANALYTICAL RESULTS: |
| Loss @ 105ºC (water): |
2 % |
| Ash Content @ 550ºC |
90.1 % |
| Carbonates (%) : |
1.3 % |
| Chlorides (%): |
Negative |
| Sulfates (%): |
Negative |
METAL
(REPORTED AS OXIDE) |
SAMPLE
REPORTED PERCENT
(normalized) |
| Aluminum (as Al2O3) |
LT 0.2 |
| Calcium (as CaO) |
LT 0.2 |
| Chromium (as Cr2O3) |
LT 0.2 |
| Copper (as CuO) |
LT 0.2 |
| Iron (as Fe2O3) |
65.1 |
| Potassium (as K2O) |
0.9 |
| Magnesium (as MgO) |
LT 0.2 |
| Manganese (as MnO) |
0.2 |
| Molybdenum (as MoO3) |
LT 0.2 |
| Sodium (as Na2O) |
2.5 |
| Nickel (as NiO) |
LT 1.4 |
| Phosphorus (as P2O5) |
LT 0.2 |
| Silicon (as SiO2) |
0.5 |
| Strontium (as SrO) |
LT 0.2 |
| Zinc (as ZnO) |
30.6 |
| LT = Below the Actual Detection Limit |
|
Photograph #1: Sample as recieved
STEREOMICROSCOPIC ANALYSIS:

Residue sample: Picture #2: Mag 15X |

Residue sample: Picture #3: Mag 30X |

Residue sample: Picture #4: Mag 45X |

45X Residue sample: Picture #5: Mag 60X |
The foregoing laboratory report by Huguenot Labs, Inc. ("Huguenot Laboratories.") is intended solely as a report of the results of the analytical laboratory procedures undertaken by Huguenot Labs.
pursuant to the request for laboratory work received by it. Huguenot Labs. warrants only that this report accurately reflects the procedures followed and the results obtained as set forth herein. Huguenot
Labs. makes no other warranty or representation of any kind, express or implied. The exclusive remedy against Huguenot Labs. for any cause or action relating to this report is a claim for damages not to
exceed any price paid for the report, without regard to whether any such claim is based upon breach of warranty, tort, or any other basis.